XT+
XT+ control panels are multi-area releasing control modules complying with UL 864 10th Edition. Up to 15 releasing modules may be connected to a master fire alarm control panel. Each releasing module can accommodate a separate hazard defined by two specific zone.
Each XT+ unit is equipped with a 5.25 A power supply (120 VAC or 240 VAC) to power releasing modules and attached solenoids / actuators. Each releasing area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All releasing areas may have up to 7 serially-connected status indication and control units or ancillary relay boards.
Programmable output duration
Countdown indicator shows time until release in seconds
Mode select and manual release controls per area
Monitored remote manual release input
Monitored remote abort input
Monitored remote mode select input
Monitored remote released pressure switch input
Serial connections for status units and ancillary boards
UL 864 10th Edition Listed
Up to 2 releasing areas / hazards per XT+ unit
Dual releasing outputs for each area (configurable as Main/Reserve)
First and second stage NAC outputs for each area
First and second stage volt free changeover relays for each area
Released volt-free relay per area
Trouble volt-free relay per area
Programmable releasing delays